VK681 K8.0 4:12 MODEL V-BB SPECIFIC APPLICATION ATTIC SPRINKLER

Manufacturer: Viking

2 Configurable Products

Qty

Finish Material

About

The VK681 K8.0 Model V-BB (Back to Back) Attic Sprinklers with a 4:12 < 7:12 pitch are UL Listed for both wet and dry pipe systems in combustible and non-combustible sloped attic spaces, and can be installed with steel or CPVC piping. (CPVC is allowed on wet pipe systems only.) When used with Viking's Model V-SD (Single Directional) and VK696 Attic Upright sprinklers, it is possible to utilize a single line of piping at the attic peak, eliminating the need for branch lines and greatly reducing the number of required sprinklers and associated materials. The Model V-BB is a glass bulb design with a temperature rating of 200° F, and is offered in either standard brass or ENT plating for areas subject to corrosion.  The Viking Model V-BB Attic Sprinkler provides a reduced response time due to its narrow ridge spacing of 6 ft (1,8 m) and long throw pattern (up to 30 ft in each direction measured horizontally).

Product Files

Title Type Language Link
Technical Data Sheet Technical Data and Instructions en
UL Certificate of Compliance Approval Certificates en