VK638 K8.0 QUICK RESPONSE EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (CORRIDOR)

Manufacturer: Viking

8 Configurable Products

Qty

Finish Material

Temperature

About

Horizontal Sidewall, Quick Response, 8.0 K Factor, Large Orifice, Extended Coverage, Horizontal Sidewall, Corridor Sprinklers (wide-throw), Sprinkler, Light Hazard Only, (General reference only - Always refer to technical datasheet for accurate listings and approvals)

Viking's Model VK638 Quick Response Extended Coverage Horizontal Sidewall Sprinkler is designed specifically to protect corridors, hallways, decks, walkways, and any other application where a wide spray pattern is optimal. The VK638 is cULus Listed for Light Hazard occupancies and has a K-factor of 8.0 (115). 

The VK638 uses Viking’s patented flow-shaper technology to provide larger coverage areas at lower flow and pressure requirements. The sprinkler is cULus Listed for 28 x 12 ft (8,5 x 3,7 m) and 28 x 14 ft (8,5 x 4,3 m) coverage areas, with the deflector installed up to 12 in (305 mm) below the ceiling. The 28 x 12 ft (8,5 x 3,7 m) coverage area is unique in the industry, providing a significant flow and pressure advantage for fire sprinkler systems where this area of coverage can be applied.

Product Files

Title Type Language Link
Technical Data Sheet Technical Data and Instructions en
Underwriters Laboratories Approval Certificates en